SERIES: PSE-3000 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
FEATURES
•
•
•
•
•
•
redundant (N+1) operation
blind mate connections for hot-swap
constant power (CP) mode
harmonic correction to EN61000-3-2, Class A
DROOP current sharing
single I/O connector for AC input, DC output
& signals
• remote on/off control
• power good signal
• optional 19” four slot power shelf
•
•
•
•
•
up to 3000 W continuous power
80 PLUS Platinum Efficiency
PoE output isolation; (1500 Vrms to ground)
high power density - 33.48 W/in3
PMBusTM communication for monitoring &
control
• dual fan forced cooling with speed control
• front to back (-F) and back to front (-B)
airflow versions
• power factor correction
• 3.3 Vdc (2A) standby voltage
rt
, I
nc
.
T
o
of N
C
Rheinla
nd
UV
h A
ca
meri
US
MODEL
output
voltage
output
current
output
power2,3
ripple
and noise1
efficiency4
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
PSE-3000-48-F
48
62.5
3000
480
94
PSE-3000-48-B
48
62.5
3000
480
94
PSE-3000-54-F
54
55.5
3000
540
94
PSE-3000-54-B
54
55.5
3000
540
94
Notes:
1.
2.
3.
4.
5.
Measured at 20 MHz bandwidth at an oscilloscope jack on the output with 0.1 µF ceramic and 10 µF aluminum electrolyitc capacitors.
At 90~180 Vac input, maximum of 1500 W.
At 180~264 Vac input, maximum of 3000 W.
At 230 Vac input, 3000 W. Meets 80 PLUS platinum efficiency requirements.
All specifications measured at: Ta=25°C and 220 Vac input voltage unless otherwise specified.
PART NUMBER KEY
PSE-3000 - XX - X - CXX
Base Number
Reserved for Custom
Configurations
Output Voltage
Airflow Direction:
F = AC input connector to DC output connector
B = DC output connector to AC input connector
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PSE-3000 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 07/22/2015 │ page 2 of 19
INPUT
parameter
conditions/description
min
voltage
typ
90
frequency
47
current
at 90 Vac, 1500 W
at 180 Vac, full load
inrush current
at 115 Vac, cold start
at 230 Vac, cold start
units
264
Vac
63
Hz
20.2
18.5
Arms
Arms
20
40
leakage current
power factor correction
max
at 230 Vac, full load
A
A
1.5
mArms
max
units
0.99
OUTPUT - V1 (MAIN OUTPUT)
parameter
conditions/description
min
typ
line regulation
±3
load regulation
±3
load capacitance
transient response
50% step load, 1A/µs slew rate, recovery to 1%
within 1 ms
start-up time
%
%
30,000
μF
3
%
5
at 230 Vac, full load
remote sense
between both output terminals
0.5
V
current share accuracy (Droop)
over 25% to 100% load
±10
%
LED indicator
12
s
hold-up time
ms
AC OK: “green” to indicate AC above the lower
limit that is required to sustain normal operation
DC OK: “green” to indicate module in normal
operating condition
OUTPUT - V2 (STANDBY OUTPUT)
parameter
conditions/description
min
output voltage
typ
max
3.3
output current
0
ripple and noise1
units
Vdc
2
A
33
mVp-p
line regulation
±5
%
load regulation
±5
%
load capacitance
transient response
50% step load, 1A/µs slew rate, recovery to 1%
within 1 ms
start-up time
Notes:
1000
µF
3
%
5
s
max
units
60
120
Vdc
%
62.5
2.6
A
A
1. Measured at 20 MHz bandwidth at an oscilloscope jack on the output with 0.1 µF ceramic and 10 µF aluminum electrolyitc capacitors.
PROTECTIONS
parameter
conditions/description
min
over voltage protection
V1: latch off
V2: latch off
110
over current protection
V1: constant current inception
V2: hiccup
over temperature protection
at full load, auto recovery
typ
55
cui.com
°C
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PSE-3000 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 07/22/2015 │ page 3 of 19
SAFETY & COMPLIANCE
parameter
conditions/description
min
insulation safety rating / test
voltage
input to output, reinforced
input to chassis, basic
3,000
1,500
typ
max
units
Vrms
Vrms
isolation voltage
output to output
output to chassis
signals to chassis/ground
V2 to chassis/ground
1,500
1,500
1,500
100
Vrms
Vrms
Vdc
Vdc
grounding
The main output V1 is “floating” and not
referenced to chassis/ground.The output control
and status signals are referenced to the V2 output
return connection.
safety approvals
EN60950-1:2006+A11+A1+A12, IEC609501:2005+Amd 1, CAN/CSA-C22.2 No.60950-107+A1:2011, UL 60950-1:2007 R12.11(NRTL
Route), EEC/93/68/LVD, 2006/95/EC LVD
conducted emissions
FCC 15 Sub Part B, EN55022, Class A: 3dB margin
tested with resistive load
radiated emissions
FCC 15 Sub Part B, EN55022, Class A: 3dB margin
tested with resistive load
harmonic compliance
EN/IEC 61000-3-2:2009, Class A Harmonic Limits
Compliance Level: 230 Vac line voltage; 100%
output load
flicker
EN/IEC 61000-3-3:2009 limits as specified in the
standard: flicker and voltage fluctuations
electrostatic discharge
EN/IEC 61000-4-2, ±8 kV operational air
discharge, ±8 kV contact discharge: all parameters
to remain within limits, test set up to be defined
RF electro-magnetic field.
amplitude modulated
EN/IEC 61000-4-3 80~1000 MHz, 10V/m, 80%
AM Modulation (1 kHz): all parameters to remain
within limits, test set up to be defined
immunity to fast
transients
EN/IEC 61000-4-4 Power lines: ±2 kV: all
parameters to remain within limits, test set up to
be defined
surges (mains)
EN/IEC 61000-4-5 ±1 kV line to line, ±2 kV line to
earth, Criteria A: all parameters to remain within
limits, test set up to be defined
RF continuous
conducted
EN/IEC 61000-4-6 150 kHz~80 MHz 3Vrms 80%
AM (1 kHz), Criteria A: all parameters to remain
within limits, test set up to be defined
voltage dips/
interruptions
IEC 61000-4-11 30% reduction for 10 ms, 60%
reduction for 100 ms: Reset is permitted must be
selfrecovering. Additionally, the PSU shall not latch
up during any brownout condition.
MTBF
as per Telcordia SR-332, Issue 2, Sept 2006
component stress method at Ta=25°C
916,000
hours
RoHS
2011/65/EU
WEEE
2012/19/EU
ENVIRONMENTAL
parameter
conditions/description
operating temperature
full load, no derating
storage temperature
operating humidity
min
max
units
0
50
°C
non-condensing
-40
70
°C
non-condensing
10
90
%
5
90
%
storage humidity
cui.com
typ
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PSE-3000 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 07/22/2015 │ page 4 of 19
ENVIRONMENTAL (CONTINUED)
parameter
conditions/description
acoustic
ISO 7779-1999
cold1
IEC 68 Part 2 – 1: at -10°C minimum for 4 hours
dry heat
IEC 68 Part 2 – 2: at 50°C minimum for 4 hours
damp heat, cyclic
IEC 68 Part 2 – 30: at 20~45°C, 30~95 %RH
low air pressure (operating)
IEC 68 Part 2 – 13: at 10,000 feet, 697 mbar
vibration (sinusoidal)
IEC 68 Part 2 – 6: at 10~58 Hz, 0.075 mm;
58~500 Hz, 10 m/s2, 1 octave/minute, 10 cycles/
main axis
1
G
shock
IEC 68 Part 2 – 27: at 300 m/s2, 11 ms, half sine
wave 3 shocks/main axis
30
G
bump
IEC 68 Part 2 – 29: at 150 m/s2, 6 ms, half sine
wave 900 bumps/main axis
15
G
Notes:
min
typ
max
units
60
dB LpAm
1. The module shall start up at -10°C, however it is not required that the full specification is achieved until the operational internal temperature has risen to 0°C.
MECHANICAL
parameter
conditions/description
dimensions
14.00 x 4.00 x 1.60 (355.6 x 101.6 x 40.6 mm)
min
typ
2.01
integral fans
material flammability
UL 94V-0
AC input
IEC320/C14
DC output
FCI PwrBlade P/N 51939-661LF
mates with FCI P/N 51915-351LF
MECHANICAL DRAWING
units: inches [mm]
tolerance:
X.XX ±0.02 [0.50]
X.XXX ±0.010 [0.25]
D1 D2 D3 D4 D5 D6
C1 C2 C3 C4 C5 C6
B1 B2 B3 B4 B5 B6
P1
P2
P3
P4
P5
A1 A2 A3 A4 A5 A6
cui.com
P6
P7
units
inches
weight
cooling / airflow
max
P8
P9
kg
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PSE-3000 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 07/22/2015 │ page 5 of 19
DC PIN ASSIGNMENTS
PIN
FUNCTION
DESCRIPTION
P1, P2, P3
V (-VE/return)
V1 (-VE) output terminal
P4, P5, P6
V (+VE)
V1 (+VE) output terminal
P7
earth/chassis ground
protective/safety earth
P8
neutral
neutral or AC line#2
P9
signal
pin
column
“1”
signal
pin
column
“2”
signal
pin
column
“3”
signal
pin
column
“4”
signal
pin
column
“5”
signal
pin
column
“6”
line
hot/AC line#1
A1
I2C address A0
I2C address - LSB
B1
I2C address A1
I2C address bit
C1
I2C address A2
I2C address - MSB
HIGH / LOW LEVEL
Imax
internal pull up to 3.3 V
D1
REMOTE_ON_L
signal pin status
output status
open circuit
“off”
logic “1”
“off”
logic “0”
“on”
3.3 mA
A2
DC_OK_L
“L” to indicate DC output is within regulation,
there is no internal pull up resistor and it should
be provided externally to support VCEO ≤ 20 Vdc,
Ic ≤ 5 mA dc
B2
AC_OK_L
“L” to indicate AC above lower limit that is required
for sustain normal operation, there is no internal
pull up resistor and it should be provided externally
to support VCEO ≤ 20 Vdc, Ic ≤ 5 mA dc
>2.1 V
2.1 V
2.1 V
2.1 V
2.1 V